trusted seller
Relay Test Set (ZNT33) Relay Test Set (ZNT33) Relay Test Set (ZNT33)

Relay Test Set (ZNT33)

303100 INR/Unit

Product Details:

  • Accuracy 1%
  • Resistant Feature Shockproof, Rustproof, Heat Resistant
  • Pressure Non-pressurized device
  • Usage & Applications Testing and Calibration of Protective Relays
  • Product Type Relay Test Set
  • Material Mild Steel (MS) Body, Bakelite Panel
  • Measuring Voltage Range 0-260 V AC/DC
  • Click to view more
X

Relay Test Set (ZNT33) Price And Quantity

  • 303100 INR/Unit
  • 1 Unit
  • Approx. 500 VA
  • Portable, Bench-top
  • High Quality Brass Terminals
  • 230 V AC, 50 Hz
  • 0-5 A AC
  • Analog Meter
  • Natural Air Cooled
  • IS Specification
  • Manual and Automatic Test Modes
  • Rotary Switch for Range Selection

Relay Test Set (ZNT33) Product Specifications

  • Non-pressurized device
  • 50/60 Hz
  • Standard Compact
  • Testing and Calibration of Protective Relays
  • Overload and Short Circuit Protection
  • Relay Test Set
  • 340 mm x 280 mm x 180 mm
  • Approx. 8 Kg
  • 1%
  • Yes, High-grade insulated casing
  • Grey & Blue
  • Mild Steel (MS) Body, Bakelite Panel
  • 0C to 55C
  • Shockproof, Rustproof, Heat Resistant
  • 0-260 V AC/DC
  • Approx. 500 VA
  • Portable, Bench-top
  • High Quality Brass Terminals
  • 230 V AC, 50 Hz
  • 0-5 A AC
  • Analog Meter
  • Natural Air Cooled
  • IS Specification
  • Manual and Automatic Test Modes
  • Rotary Switch for Range Selection

Relay Test Set (ZNT33) Trade Information

  • All India

Product Description

The Set is in two units.

i) Current Source, Voltage Source & Measuring Unit

Current circuit, AC & DC voltage circuits, protective circuit, contactor, measuring circuits etc. will all be housed within sturdy MS cabinet. Also meters, terminals, indicators, regulator knobs, timer display etc. will be fitted on the horizontal panel of the same cabinet which can be approached by opening the top hinged lid. Wheels will be provided for easy movement.

ii) Phase Shifter Unit:

Static type phase shifting transformer will be housed within this MS unit. Input output interconnection socket, Phase

Shifting Coarse & Fine control knobs are fitted on the horizontal plane of the sturdy MS cabinet, which can be approached by opening the top, hinged lid.

Special Features:

Fault phase voltage adjustable between 0 to 100%.

Fault current adjustable between 0 to 100%.

Phase angle adjustment & measurement 00 to 3600.

Digital Time Interval meter.

Voltage & Current indications by digital meters.

While testing is in phase-to-phase fault mode, selectable phase currents i.e. say, R-Y will be in opposition. The neutral & remaining third phase current, B, will then be absent. For this, selectable switch is provided.

Technical Features:

Input Voltage : 415V, 3 phase, 4 wire, 50Hz. AC.

Output(s)

[a] Test Current:

0 to 1, 5, 10, 25 & 50A having 0 - to 100% regulation in each tap. Rated maximum burden: 250VA.

Duty cycle:

i) Continuous upto 10A.

ii) 25A & 50A outputs are rated for intermittent duty cycle ie. 25A - 3 minutes ON& 50A - 30 secs ON

[b] Test Voltages:

AC voltage source:

110 volts, phase to phase, 63.5 volts phase to neutral, and 3 phase 50Hz. AC continuously variable from 0 to 100%. Rated maximum burden: 250VA.

Fixed DC voltage source:

Isolated fixed

30V/110V/220V DC of 100VA, without metering will be available for 30 mins.

[c] Phase Angle Variation:

0 to 3600 between voltage & current.

[d] Time measurement:

0-9.999secs. & 0-99.99secs. in two steps.

Current Circuit:

Loading Transformer:

Double winding loading transformer of suitable burden to provide corresponding current output specified before.

Measuring CT:

Multi-ratio wound primary current transformer:

Ratio: 1-5-10-25-50/1A with current range selectable rotary switch.

Variable Auto-transformer:

[1 no. for each phase] For smooth variation of current output at various ranges selected.

Tripping circuit:

The current output would be cutoff incase of any overload or even if the relay under test actuates.

Metering: CT operated ammeter

Range: 0 to 1A AC. Scaled: 0 to 100% for all the selected current ranges. Accuracy: 1%. Resolution: 0.1%.

Voltage Circuit:

Variable Auto-transformer:

[1 no. for each phase] For smooth variation of voltage output from zero to rated voltage. Fault mode selector switch

Metering: Voltmeter with phase selector.

Range: 0 to 200V.

Accuracy: 1%. Resolution: 0.1V.

DC Voltage circuit:

Double wound multitap isolated transformer is provided for fixed DC voltage sources. 30V/110V 220V are selected one at a time by selector switch.

Phase Shifter Circuit:

Static Type Phase Shifting Transformer

Primary Voltage: 415V, 3 ph., 50Hz. AC.

Secondary Voltage: 110V, 3 ph. 50Hz. AC.

0 to 3600 phase angle variation by coarse and fine control.

Coarse control will be in steps of 600 while fine control will be of + 300

Capacity: 250VA.

Metering:

Phase Angle Meter: 3600.

Resolution: 10.

There will be provision for phase selection by selector switch.

Timer Circuit:

Measuring Range Resolution

9.999secs. 0.001sec.

99.99secs. 0.01sec.

Display : Seven segment LED.

Accuracy : 1%.

Terminals to relay contacts.

Reset push button.

Selector for NO & NC contact.

Potential free start timer for opening or closing of auxiliary contact of the contactor.

Interconnection Cable:

Necessary cables of 1-meter length along with plug will be provided for interconnection between two units.

Mains Input Cable:

Four-core cable of 5 meters length will be provided. All the meters will be digital type.

Documents:

Operation Manual(Instruction Manual)

Works Test Report

Warrantee Certificate



Versatility in Relay Testing

The ZNT33 Relay Test Set is engineered for diverse testing scenarios, supporting both manual and automatic modes. Its wide current and voltage measuring ranges, coupled with a rotary switch for range selection, cater to comprehensive calibration needs in industrial and laboratory settings.


Robust Safety & Durability

Safety is prioritized with built-in overload and short circuit protection. The high-quality insulated casing, constructed from mild steel and Bakelite, ensures reliability even in demanding environments. Its shockproof and heat resistant qualities further enhance operational longevity.


Efficient Portable Design

With a compact size and a weight of approximately 8 kg, the ZNT33 is easy to transport and install wherever needed. Its portable, bench-top mounting style makes it ideal for on-site relay testing and quick deployment in various industrial locations.

FAQ's of Relay Test Set (ZNT33):


Q: How do you operate the Relay Test Set (ZNT33) for relay calibration?

A: To use the ZNT33, connect the relay under test to the brass terminals, set the desired output current or voltage using the rotary switch, and select either manual or automatic test mode. The analog meter provides real-time measurements, allowing precise calibration and testing.

Q: What protective features does the ZNT33 offer during testing?

A: The test set is equipped with overload and short circuit protection as well as a high-grade insulated casing. These features safeguard users and equipment from accidental faults and electrical hazards during operation.

Q: When is manual versus automatic test mode recommended?

A: Manual mode is ideal for hands-on adjustments and monitoring, providing direct control over the testing process. Automatic mode streamlines repetitive test sequences, increasing efficiency and consistency in calibration tasks.

Q: Where can the ZNT33 Relay Test Set be utilized?

A: This test set is suitable for use in laboratories, industrial environments, and on-site locations that require the testing and calibration of protective relays. Its portable, bench-top design makes it easy to deploy wherever relay testing is needed.

Q: What standards does the ZNT33 comply with?

A: The device is manufactured in compliance with IS Specifications, ensuring it meets quality and safety standards required for professional relay testing equipment.

Q: How does the natural air cooling system benefit the device?

A: Natural air cooling minimizes maintenance requirements and reduces the risk of overheating, providing reliable operation without the need for additional cooling apparatus.

Tell us about your requirement
product

Price:

Quantity
Select Unit

  • 50
  • 100
  • 200
  • 250
  • 500
  • 1000+
Additional detail
Mobile number

Email

Other Products in 'Test Sets for Switchgear Industries' category



Works:

117, Mishrapara Road, Rathtala, P.O. Rajpur,
Kolkata - 700 149, West Bengal, India.
Back to top