TECHNICAL FEATURES:
Input Voltage : 230volts+10%, single phase, 50Hz. AC
Output(s
a) Current Output:
RANGE NO LOAD VOLTAGE(MIN.) RECOMMENDED LOAD/ UN LOAD
TIMES ON (MAX.)/OFF (MIN.)
0 - 2A 120 V CONTINUOUS
0 - 10A 40 V 15/10 MINUTES
0 - 20A 40 V 10/10 MINUTES
0 - 100A 5 V 2/10 MINUTES
0 - 200A 5 V 30 SEC/10 MINUTES
b) AC Voltage Output: Continuously variable 0 to 250 Volts AC. Capacity: 1Amps max.
c) DC Voltage Output: Continuously variable 0 to 240 Volts DC. Capacity: 0.5 Amps max.
d) Time measurement: Digital Time Interval Meter: 0-9999.9999secs.
CURRENT CIRCUIT:
Loading Transformer:
Double winding loading transformer of suitable burden to provide corresponding current output specified before.
Measuring CT:
Multi-ratio wound primary current transformer. Ratio: 2-20-200A / 2A.
Variable Autotransformer:
For smooth variation of current output at various ranges selected.
Protection: The current output would be cutoff in case of any overload or even if the relay under test actuates.
Metering: Direct reading with meter range selector.
AC VOLTAGE CIRCUIT:
For smooth variation of voltage output from 0 to 250 volts AC at 1Amps.
Metering: Digital, Range: 0 to 250V AC.
DC VOLTAGE CIRCUIT:
Separate DC voltage source with ON/OFF switch, fuse & lamp indication.
For smooth variation of voltage output from 0 to 240 volts DC at 0.5 Amps.
Isolation transformer of suitable burden is provided for DC output.
Metering: Digital, Range: 0 to 250V DC.
Provision for the Timer contact for checking protective equipment like breaker/Relay tripping.
Time Interval Meter (TIM):
Microcontroller based 8 digits Timer.
Range: 0 - 9999.9999 seconds with minimum count of 0.1 milli seconds. Accuracy 0.05%.
The Timer will be capable to record & display the tripping time of relay under test automatically.
The Time Interval meter will be suitable to measure Closing (Make) and Opening (Break) time for Relay through Potential Free contacts.
The TIM will be provided with Rest facility.
GENERAL ARRANGEMENT:
The Test Kit will be in one unit and Flight case type.Meters, Terminals, Indicators, Regulator knobs, Timer, Display etc. will be fitted on the horizontal panel of the set, which can be approached by opening the top lid. Loading transformer, Measuring CT & protection circuit etc. will also be housed within the same unit.
ACCESSORIES:
The Test set will be supplied with
i. 3 Pin Mains Input power cord -3 meters-1 no.
ii. Output connecting cables for Current Circuit & Voltage Circuits terminated with lug at one end and
crocodile clip at the other end -1.5 meters each pair.
iii. Timer output screened guard leads with connectors/ clips -1.5meters-1 pair.
iv. Earth leads with connectors/clips.
v. Leather or similar type carrying case for cables.
Dimension (Approx.): 520mm X 388mm X 315mm (LengthXWidthXHeigth)
Weight. (Approx.): 38 Kgs.
DOCUMENTS:
Operation Manual, Works Test Report, Warrantee Certificate will be supplied along with the Set.
Note: The Dimension, weight & look of the Test Set may vary at the time of manufacture due to design innovation.



Price:
Price 5000 MXN ($) / Unit
Minimum Order Quantity : 1 , , Unit
Resistant Feature : High voltage and temperature resistance, anticorrosive
Dimension (L*W*H) : 1240 x 670 x 1630 mm
Usage & Applications : Testing and seasoning of highvoltage components, industrial electrical workshops, manufacture of circuit breakers, transformers, and insulators
Protection System : Multilayer automatic protection system with grounding
Price 5000 MXN ($) / Unit
Minimum Order Quantity : 1 Unit
Resistant Feature : Shock and electrical insulations, dustproof enclosure
Dimension (L*W*H) : 185 mm x 90 mm x 120 mm
Usage & Applications : Measurement and indication of phase angle shift in electrical panels, power factor correction and laboratory testing equipment
Protection System : Overvoltage and overcurrent protection
Price 5000 MXN ($) / Unit
Minimum Order Quantity : 1 Unit
Resistant Feature : Shock, Dust & Corrosion Resistant
Dimension (L*W*H) : NA Centimeter (cm)
Usage & Applications : Testing, calibration and commissioning of protective relays
Protection System : Overload and Short Circuit Protection
Price 300000 INR / Unit
Minimum Order Quantity : 1 Unit
Resistant Feature : Corrosion and shock resistant body
Dimension (L*W*H) : 230 mm x 195 mm x 85 mm
Usage & Applications : Low resistance measurement in switchgear, circuit breakers, cables, busbars, and electrical joints
Protection System : Overload and shortcircuit protection