NTPL MAKE 3 CHANNEL TIMEANALYSER FOR CIRCUITBREAKER
TYPE NTT3CHCBTAR2
Theabove Time Analyzer is suitable to check simultaneous operation in threedifferent channels of 3 phase Power Circuit Breaker. The instrument is portableand is made with extensiveuse of integrated circuits to achieve accurate, long and trouble free service.
Mains Supply 230 volts +/- 10% 50Hz single phase AC.
No. Of Channels 3
Time Measurement 0 to 999.9m Sec., Resolution 0.1ms
Display 4 digit display for each channel.
Accuracy +/-1% +/- 1 digit.
Operation Mode Opening or closing of potential freecontact.
Latching Thisfacility is available for only clean signals of contact closing and opening withoutbouncing.
Reset Bypush button switch.
The Timer will be providedwith CLOSE OPEN and CLOSE-OPEN (C-O) push button switch incorporatingcontrol arrangement for supply of Power Source to CLOSE and OPEN coil ofCircuit Breaker under test and simultaneous start operation of the TimeAnalyzer. The timer stops with the change of status of the main contact withfeedback (potential free) from the main contacts of the circuit breaker.
The Power Source to the CLOSE and OPEN coil can be provided at extra cost by NTPL with following specifications
i. Power Supply (Type CBA ACDC2)
Input 230 volts, 50 Hz. 1 phase A.C.
Output 0 to 220V continuously variable DC.
Capacity : 2 A continuous and 10A for instantaneous for 5Sec. Duty.
Or
0to 240V continuously variable AC.
Capacity : 2 A continuous and 10Afor instantaneous for 5Sec. Duty.
Compatible with our 3 Channel Time Analyzer.
ii. Power Supply (Type CBA ACDC4)
Input 230 volts, 50 Hz. 1 phase AC.
Output 0 to 220V continuously variable DC.
Capacity: 4 A continuous and 10A for instantaneous i.e. for 5Sec. Duty.
Or
0to 240V continuously variable AC.
Capacity : 4 A continuous and10A for instantaneous i.e. for 5Sec. Duty.
Compatiblewith our 3 Channel Time Analyzer.
ACCESSORIES
Suitable interconnecting cables of approx. 5 meterslength are to be provided for interconnection between the Circuit Breaker and Time Analyzer.
Also, if Power Source is supplied along withTime Analyzer then interconnecting cables between Power Source and TimeAnalyzer will also be provided.
DOCUMENTS
Operation Manual, Works Test Report,Warrantee Certificate will be supplied along with the set.